Specification: The control panel shall be steel and rated NEMA 4, UL 508 and NFPA 99. It shall control two pump motors and have two pump Circuit Breakers with Thru-Door Operators. It shall allow each motor to be started and stopped through a Hand-Off-Auto Selector, a PLC, and various field sensors. It shall indicate various conditions through flash sequences on two Alarm indicators and an audible alarm with Silence button. Auxiliary contacts shall be provided for Pump 1 and 2 Hand-Off-Auto in Auto, General Fault.

Standard Features

  • UL 508 Listed
  • NFPA 99 Compliant
    • Redundant Control Xfmrs
    • Alarm if 2nd Xfmr Req'd
    • Alarm if 2nd Pump Req'd
  • Programmable Logic Controller
  • Door Mounted Controls
    • (2) Circuit Breaker Operators
    • (2) Hand/Off/Auto Selectors
      • Green Run Indicator
    • (2) Amber Fault Indicators
      • 1 Flash = High Temp
      • 2 Flashes = Oil Level
      • 3 Flashes = Overload Trip
      • 4 Flashes = Lag Pump
    • (2) OL Reset Pushbuttons
    • 1st Xfmr Fault Indicator
    • Alarm Horn
    • Alarm Silence Pushbutton

Power Compatibility

  • Voltage- 208/230/480V
  • Horsepower - 5 to 50 HP
  • Motor Power Options
    • Across the line Motor Starters
    • Solid State Motor Starters
    • Variable Frequency Drives